The IELR Series is designed specifically for the 35mm symmetrical DIN rail, Airpax IALHR, IULHR, and IELHR Series. Rail-Mount Magnetic circuit protectors offer the advantages of quick and easy mounting or removal, resulting in efficient and economical wiring while conserving space. These circuit protectors are available in 1, 2, 3 and 4 pole models, with a choice of handle colors with on/off and international I/O markings. These protectors comply with UL and CSA standards and meet IEC and TUV spacing requirements.
Typical applications include computers and peripherals, telecommunications, medical equipment, machine tools, and process control instrumentation. They provide a reliable performance associated with magnetic circuit protection. Mounting – These circuit protectors are designed to mount on standard 35mm DIN rails, such as 35×7.5 or 35×15 per DIN EN50022. Other specialty rails are available from suppliers that provide a means of mounting non-DIN mount components by means of special captive jam nuts.
Features
Series Trip
The most popular configuration for magnetic protectors is the series trip where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional overcurrent protection, it’s simultaneously used as an on-off switch.
Switch Only
In the event that over-current protection is not desired, the coil mechanism can be deleted, providing an excellent low cost, single or multi-pole power switch.
Insulation Resistance
100 megohm minimum at 500Vdc between all electrically isolated terminals.
Dielectric Strength
3750Vac (3750V~) shall withstand AC voltages 50/60Hz for 60 seconds between all electrically isolated terminals.
Endurance
Circuit breakers shall operate a minimum of 10,000 operations; 6,000 with rated current and voltage and 4,000 with no load.
Operating Temperature
–40°C to +85°C.
IEC 144 Classification
Type handle spacings–IP40. Terminals–IP00.
Moisture Resistance
10 days, 95 percent relative humidity at 40°C in accordance with IEC68-2-3, test C.
Salt Spray
Five percent solution at 35°C in accordance with IEC68-2-11, test K, 48 hours.
Shock
50g, 11m sec, half sine with rated current, except no current with handle down. Instantaneous units use 80 percent rated current. Test in accordance with IEC68-2-27, test Ea. This assumes that adequate end stops are used to prevent longitudinal movement of the circuit protector.
Vibration
4g, 5–500Hz (maximum double amplitude displacement 1.5mm) with rated current except no current with handle down. Instantaneous units use 80 percent rated current, in accordance with IEC68-2-6, test F, method A, one hour per plane. This assumes that adequate end stops will be used to prevent longitudinal movement of the circuit protector.