- ESM-BA.. Usage up to category 4 according to EN ISO 13849-1
- LED status indicators
- 1-channel or 2-channel control
- 2 redundant safety contacts
- Short circuit and earth fault/ground fault monitoring
Euchner ESM-BA203 Safety relay ESM
Stok kodu:
85612
Kategoriler: Emniyet Röleleri ve Kontrol Sistemleri, Röleler
Açıklama
Ek bilgi
Brand |
---|
GET A PRICE
To receive a proposal, please send your application to info@avat-industrial.com and specify the required positions and company details.
Specification
Relay outputsThe outputs are electrically decoupled and of redundant design.
Connection optionsBy using suitable wiring the following functions can be selected:
Electrical connection ratings
Other
Reliability values according to EN ISO 13849-1
- Relay start with automatic start or a start button
- Monitoring of downstream relays or contactors
- Simultaneity monitoring to monitor safety components over time
- Relay start using a monitored start button
- Short circuit monitoring to detect short circuits between the connection cables and to shut down the outputs or prevent relay starting if necessary
- Earth fault/ground fault monitoring to detect short circuits between the connection cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Housing material | Polyamide PA6.6 |
Weight | |
Net | 0,23 kg |
Ambient temperature | |
At UB = 115/230V AC | -15 ... 40 °C |
Degree of protection | IP20 |
Mechanical life | |
operating cycles | 10 x 106 |
Contact material | AgSnO2 |
Mounting method | Mounting rail 35mm according to DIN EN 60715 TH35 |
Connection | Connection terminals |
Length of control cable | |
With conductor cross-section 0.75mm2 | 1000 m |
Safety contacts 13/14, 23/24 | |
Number of safety contacts | 2 |
Operating voltage | |
AC | 230 V -10% ... +10% |
Power consumption (apparent power) | |
At 230 V AC | 3,7 VA |
Rated insulation voltage Ui | |
AC | 250 V |
Rated impulse withstand voltage Uimp | |
Leakage path/air gaps | 4 kV |
Overvoltage category according to IEC EN 60664-1 | 3 |
Rated supply frequency | 50 ... 60 Hz |
Degree of contamination (external, according to EN 60947-1) | 2 |
Connection cross-section | 0,14 ... 2,5 mm? Connection terminal (size) |
Test voltage | |
Control system/contacts | 2,5 kV |
Control voltage | |
On S11 | 24 V 18,6 ... 26 V Start button |
Control current | |
S11...S14 | 40 mA |
LED indicator | 2 status displays (green) for relays K1 and K2 |
Safety contacts 13/14, 23/24 | |
Type of output | |
NO | Relay contacts, floating and positively driven (redundant) |
Switching voltage | |
AC | max.250 V |
DC | max.24 V |
Switching current | min.20 mA at 24V |
Fusing | |
External contact fuses (safety circuit) according to IEC 60269-1 | 10A gG (T6A / F8A) |
Utilization category according to EN 60947-5-1 | |
AC-15 | 3A , 250V |
DC-13 | 3A, 24V |
AC-12 | 6A ohmic load, 250V |
DC-12 | 6A ohmic load, 24V |
Breaking capacity according to UL | 6A 250V AC / 2A 24V DC |
In compliance with | EN 60439-1: 1999 + A1: 2004; EN 60947-1: 2007; EN 60947-5-1: 2004; EN 60947-7-1: 2002; EN 61000-6-2: 2005; EN 61000-6-3: 2007; EN ISO 13849-1: 2015; EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015; EN 60204-1: 2007 |
Performance Level | PL e |
Category | 4 |
PFHD | 1.2 x 10-8 |
Number of switching cycles | |
? 3 A at 24 V DC | max.22500 1/Jahr |
? 0.1 A at 24 V DC | max.400000 1/Jahr |
? 1 A at 24 V DC | max.100000 1/Jahr |
Mission time | 20 y |